The thermostat as a all in one temperature controller, users can be flexibly set for air conditioning, floor heating, or ventilation controller. Among them: as the air conditioning temperature controller, you can choose to set as one way three line two control valve, or one way three line one control valve control single cooling or heating, or two way two line valve control dual cooling and heating, support high, medium, low, automatic wind speed, local room temperature detection; When used as the floor heating thermostat, it can support the maximum 2.5A load output control; As a ventilation controller, it can support high, medium and low wind speed control.
the thermostat can automatically request the gateway synchronization time, support the reporting of the actual working status of cold and hot valves and fans, and support linkage control.
Operating instructions
1. Local Control
a) ON/OFF:Hold down the open key for 1 second to switch the machine on and off.
b) Wind speed control: press the function button to switch the low speed, medium speed, high speed and automatic mode under the working mode of air conditioning and ventilation.
c) Temperature control: press the up or down button to adjust the set temperature under the working mode of air conditioning and floor heating.
d) Air conditioning mode selection:Under the working mode of air conditioning, keep pressing the function key to cycle switch cooling, heating and ventilation in the mode of air conditioning.
2. Local menu
a) When the machine is off, keep pressing the function key for 1 second to enter the local menu for setting; In the local menu setting mode, press the function key to select the menu item, press the up and down key to modify the setting parameters; When the setting is completed, press the power button to save the parameters.
b) Menu function parameters are described below:
Menu | Functional specifications | parameter |
H1 | Powered | ON-Normally open; OF-Normally close; bF- Restore power down |
H2 | temperature unit | Not support |
H3 | Set temperature ceiling | 5~45 |
H4 | Set temperature limit | 5~45 |
H5 | Key lock | Not support |
H6 | Display mode | Not support |
H7 | Low temperature protection | ON-Open; OF-Close |
H8 | Temperature compensation | 0~5 |
H9 | Machine model | 0-Air conditioning; 1-Not support; 2-Floor heating; 3-Ventilation |
HA | Temperature limit of external sensor | |
Hb | Valve start temperature difference | 0~5 |
HC | Air conditioning fan maintenance | ON-Open; OF-Close |
Hd | Air conditioning control | 26-two control;; 46-four control |
HE | mailing address | 0(fixed) |
HF | Display brightness mode | ON-Normally open; HF-Half Bright; OF-Turn off screen |
HH | Update filter time | Not support |
3. Wireless network registration/removal
a) Network registration: after the user starts the registration status of the main control gateway, press the "up" and "down" keys for 2 seconds at the same time in the shutdown state to start the network registration. During the registration process, the wireless status icon flashes.
b) Network removal: After the user starts the removal state of the main control gateway, press the "up" and "down" keys for 2 seconds at the same time in the shutdown state to start network removal..
c) In the unregistered state, the wireless status icon keeps flashing slowly.
4. Wireless network linkage
a) This product supports 4 groups of device association. The first group can be associated with 1 device, and each other group can be associated with up to 5 devices.
Group 1: Thermostat status report;
Group 2: Switch on/off the device when the corresponding thermostat is on.
Parameter setting
1. Parameter number:01 – set all in one service mode.
Bits Length:1 byte
Parameter values:
01 – Air conditioning thermostat working mode;
02 – Floor heating thermostat working mode;
03 –Ventilation controller operating working mode.
The network should be removed and added again after the device's working mode is modified.
2. Parameter number:02 – Set and temperature control address.
Bits Length:1 byte
Parameter values: 0~255,0x00(default).
3. Parameter number:03 – reserve.
4. Parameter number:04 – Set power on switch machine mode.
Bits Length:1 byte
Parameter values: 0~1,0x00 Electricity power off(default),0x01 Electricity power on.
5. Parameter number:05 – reserve,set Time Zone Number.
6. Parameter number:06 – Set the temperature controller specified parameters.
Bits Length:4 byte
Parameter values: Byte 1, 2 for the thermostat register address; Bytes 3 and 4 set the parameters for the corresponding registers. See multi-function thermostat control register parameter table for details.
Attention
1. In the process of use, if you encounter thermostat failure, please contact the supplier in time, do not disassemble and repair privately, so as to avoid damage.
2. Switch housing has heat dissipation through hole. When cleaning, pay attention to avoid water vapor penetrating into the box cover, which may lead to circuit damage and short circuit.
Technical data
Working Voltage | 220V AC |
Power Consumption | <0.3W |
Switching load |
Cold valve single way maximum 2.5A@220VAC Hot valve single way maximum 2.5A @220VAC Fan single path maximum 1.5A@220VAC
|
Radio Frequency | 868.4 MHz – China/Europe 908.4 MHz – America 921.4 MHz – Australia 869.2 MHz – Russia |
Transmitting distance | Indoor straight-line distance is 30 meters Outdoor distance is 50 meters as the crow flies |
Temperature Controlling Range | -10℃~+50℃ |
Relative Humidity | ≤95%RH |
External Dimension | 86 x 86 x 34 mm |
Internal Dimension | 59 x 61 x 23 mm |
Execution standard |
Z-Wave supports commands
Root Device:
Generic Deice Type =
GENERIC_TYPE_THERMOSTAT
Specific Device Type =
SPECIFIC_TYPE_THERMOSTAT_GENERAL
Support Command Class =
COMMAND_CLASS_ZWAVEPLUS_INFO,
COMMAND_CLASS_MANUFACTURER_SPECIFIC,
COMMAND_CLASS_VERSION,
COMMAND_CLASS_POWERLEVEL,
COMMAND_CLASS_ASSOCIATION_GRP_INFO,
COMMAND_CLASS_ASSOCIATION,
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION
COMMAND_CLASS_CONFIGURATION,
COMMAND_CLASS_THERMOSTAT_MODE,
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE,
COMMAND_CLASS_THERMOSTAT_FAN_MODE,
COMMAND_CLASS_THERMOSTAT_FAN_STATE,
COMMAND_CLASS_THERMOSTAT_SETPOINT
COMMAND_CLASS_SENSOR_MULTILEVEL